4. WIRING
Power supply requirements, 12-36Vdc, note installation
recommendations as follows:
Terminal Strip: SMKDSP1.5/2-5.08 Phoenix contact
A. Cable Requirements
Two core shielded cable
• Cable outer diameter: 0.3to 0.47˝ (9-12mm)
Required for proper installation with cable gland option
Wire Gauge: 14-22 AWG (multi-strand or solid)
B. Wiring Instructions
• Do not run pressure transmitter cable / wires within the same conduit as high
voltage (line power) line to reduce the potential for noise (interference).
Use dedicated conduit on GC52 cables / wires for optimum results.
• Cable diameter, specified above, must be maintained when using the Cable
Gland termination to retain environmental ratings.
• When connecting shield / drain wire, only connect one end which should be at
the received ground.
• Wire stripping instructions; remove cable jacket 2-3˝ and strip wires 0.25˝.
Shield / drain wire should not be exposed at the pressure transmitter termination.
Terminal box
Display (board)
Shield
Power source
Receiver
Transmission cable
CASE
DISPLAY
CAP
Inside sensor Line
LCD holder
Notch
Transmission cable
(Twist)
Sheath