Comparator Setting Mode
Loop Check Mode
Measurement Mode
P
ress < 3 sec.
Press > 3 sec.
MODE
MODE
(Output1. Comparator
setting point A)
MODE
After 1 second
a-1
50.0
XW
Message displayed
Set any desired value within
the –1999 to 1999 range with
Up/Down keys
(Output1. Comparator
setting point b)
M
ODE
After 1 second
b-1
10.0
XW
Message displayed
Set any desired value within
t
he –1999 to 1999 range with
Up/Down keys
(Output1. Comparator
on delay time)
MODE
After 1 second
on1
0.00
XW
Message displayed
Set any desired value within
the 0 to 2 second range with
Up/Down keys
(Output1. Comparator
off delay time)
MODE
After 1 second
of1
2.00
XW
Message displayed
Set any desired value within
the 0 to 2 second range with
Up/Down keys
(Output2. Comparator
setting point A)
MODE
After 1 second
a-2
50.0
XW
Message displayed
Set any desired value within
the –1999 to 1999 range with
Up/Down keys
(Output2. Comparator
setting point b)
MODE
After 1 second
-10.0
XW
Message displayed
Set any desired value within
the –1999 to 1999 range with
Up/Down keys
(Output2. Comparator
on delay time)
MODE
After 1 second
on2
0.10
XW
Message displayed
Set any desired value within
the 0 to 2 second range with
Up/Down keys
(Output2. Comparator
off delay time)
MODE
After 1 second
of2
1.00
XW
Message displayed
Set any desired value within
the 0 to 2 second range with
Up/Down keys
(Loop check mode)
After 1 second
lop
0.0
XW
Message displayed
Set any desired value within
the –1999 to 1999 range with
Up/Down keys
MODE
b-2